Tools
Educational protection tools.
Three simplified illustrations of questions that come up in protection work: how two overcurrent relays compare at one fault current, how breaker-failure timers interact, and the order of events when a feeder fault is cleared. They run entirely in your browser and send nothing to us.
A · Coordination
Overcurrent time-margin check
Two inverse-time overcurrent relays with optional definite-time high-set stages. The tool calculates each relay's operating time at the fault current you select and compares the difference with the margin you enter.
This is a check at one current value, not a coordination assessment. Move the fault current across the range to see where the margin is smallest; a real study also considers minimum and maximum fault levels, CT performance, breaker data and the actual relay implementation.
Click or drag on the chart, or use the fault-current slider. Chart shows 0.01–100 s; operating times outside this range are clipped on the chart but reported in full in the results.
Educational illustration only. Project-specific protection decisions require verified system data and engineering review.
Curves, equations and units
IEC 60255-151 (IEC curves): t = TMS · k / ((I / I>)α − 1)
SI: k = 0.14, α = 0.02 · VI: k = 13.5, α = 1 · EI: k = 80, α = 2 · LTI: k = 120, α = 1
IEEE C37.112 (as also given in IEC 60255-151): t = TD · (A / ((I / I>)p − 1) + B)
MI: A = 0.0515, B = 0.114, p = 0.02 · VI: A = 19.61, B = 0.491, p = 2 · EI: A = 28.2, B = 0.1217, p = 2
Currents are primary amperes; times are seconds. The multiplier is applied directly as in the equations above. Some relays use a different time-dial scale for IEEE curves, so a "TD" value from a relay may not be directly comparable.
Assumptions, valid ranges and limitations
- The inverse characteristic is applied from 1.05 × I>; below that the relay is shown as not operating. This threshold is an assumption of this tool — actual relays define their own start value (one manufacturer's implementation, for example, uses 1.1 × I>).
- Above 20 × I> the operating time is held constant, consistent with the end of the effective range of the characteristic described in IEC 60255-151. Individual relays may differ.
- A high-set stage, when enabled, operates after its definite time if the current is at or above I>>; the relay operates at whichever stage is faster.
- Relay timing tolerances, CT errors and saturation, breaker interrupting time, relay overshoot, reset characteristics, DC offset and directional or voltage-dependent functions are not modelled.
- Accepted inputs: pickup 10–20 000 A, multiplier 0.02–1.20, high-set 10–100 000 A and 0–5 s, required margin 0.10–1.00 s, fault current 100 A–40 kA. Out-of-range entries are flagged and the last valid value is kept.
- The equations and coefficients were checked against published IEC 60255-151 curve tables. The tool itself has not been validated against a specific relay and should not be used to set one.
B · Breaker failure
Breaker-failure timing demonstration
A simplified 50BF scheme with a current check, a retrip timer t₁ and a backtrip timer t₂. Choose a scenario and play the sequence, then read the traces like a disturbance record. Shortening t₂ towards the breaker's interrupting time shows how a healthy clearance can turn into an unwanted backtrip.
The timings are examples for illustration, not recommended settings.
Educational illustration only. Project-specific protection decisions require verified system data and engineering review.
Simplified assumptions in this model
- The fault starts at t = 0; protection operates at 20 ms and initiates breaker failure.
- Both timers start when protection trip AND current check are present, in 1 ms steps, and reset when either drops.
- The current check resets 12 ms after the current is interrupted; the protection trip drops 20 ms after.
- The same interrupting time is used for the faulted breaker and the adjacent breakers.
- The suggested minimum for t₂ is breaker time + current-check reset + an assumed 40 ms margin, within this model only.
- Real schemes differ: logic, timer behaviour, current-check algorithms, auxiliary-contact use, breaker performance, communication delays and system requirements all depend on the installation and the relay implementation.
C · Selectivity
Feeder fault sequence
The order of events when a feeder relay clears a fault while the incomer relay times as backup, followed by a single auto-reclose. A permanent fault leads to a second trip and lockout. Nothing runs until you start it.
Educational illustration only. Project-specific protection decisions require verified system data and engineering review.
Assumptions used
- Feeder relays
- IEC SI · I> 400 A · TMS 0.05
- Incomer relay
- IEC SI · I> 1200 A · TMS 0.14
- Breaker time
- 55 ms
- Reclose dead time
- 1.0 s, one shot
Event sequence
Operate times are calculated from the IEC 60255-151 standard inverse curve. Pickup times and the event order are simplified, and no measured values are shown.